Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2022, 07:30 AM
  • 19 0091_19 0090_5192022_013745.mp4

Date
05/19/2022
W/O
0956461
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00722
PipeID
P15283
Time
12:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3100
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
202205MDM_EAST_ARTESIA_TRUNK_SECTS_1_2_3_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0090
Downstream MH
19 0091
Dir. of Survey
Upstream
Length Surveyed
167.8 ft.
Total Length
167.8 ft.
Structural Index
4
Structural Quick
5541
Structural Rating
31
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
35
Pipe schematic from manhole 19 0090 to 19 0091
MH: 19 0090MH: 19 0091upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:05AM0.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR CORRODED MISSING0.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE0.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - MISSING REBAR0.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG11.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING REBAR11.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING LONG CIRCUM REBAR45.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CORRODED MISSING REBAR49.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING CIRCUM REBAR71.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CORRODED MISSING CIRCUM REBAR78.2 ft. MGP - General Photograph - MISSING CIRCUM REBAR82.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED MISSING99.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR102.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR165.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE165.8 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG167.8 ft. MWL - Water Level, 10 %of cross sectional area167.8 ft. MWM - Water Mark, 50 %of cross sectional area167.8 ft. AMH - Downstream Manhole, Survey Begins - 1:30AM

Observation photos (9)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    65.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED MISSING

    85.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED MISSING

  • General Photograph - MISSING CIRCUM REBAR

    89.6 ft. - General Photograph - MISSING CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CORRODED MISSING CIRCUM REBAR

    96.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CORRODED MISSING CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING CIRCUM REBAR

    118.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING REBAR

    156.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING LONG CIRCUM REBAR

    156.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED MISSING LONG CIRCUM REBAR

Observations (19)

DistanceCodeObservation
167.2SRCLONG CIRCUM REBAR CORRODED MISSING
167.8AMH2:05AM
0MWL
156.5SRCMISSING REBAR
156.5SRCCORRODED MISSING LONG CIRCUM REBAR
167.2SSSBLISTERING PEELING CONCRETE
167.2SRCMISSING REBAR
0MWM
65.2SRCCIRCUM REBAR
118.3SRCCORRODED MISSING CIRCUM REBAR
85.2SRCCIRCUM REBAR CORRODED MISSING
68.6SRCCIRCUM REBAR
96.6SRCCORRODED MISSING CIRCUM REBAR
89.6MGPMISSING CIRCUM REBAR
0AMH1:30AM
122.7SRCCORRODED MISSING REBAR
167.2SAMSEVERE AGG
2SSSBLISTERING PEELING CONCRETE
2SAMSEVERE AGG

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED & MISSING
custom_field_two
1
customer
LACSD
datetime
2022-05-19T00:30:12-07:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false