Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2022, 08:37 AM
  • 02 0132_02 0131_5172022_025309.mp4

Date
05/17/2022
W/O
0941688
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02433
Time
1:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3091
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20220517MDM_DOWNEY_BELLFLOWER_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
02 0132
Downstream MH
02 0131
Dir. of Survey
Downstream
Length Surveyed
308 ft.
Total Length
308 ft.
Structural Index
5
Structural Quick
5242
Structural Rating
18
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
18
Pipe schematic from manhole 02 0132 to 02 0131
MH: 02 0132MH: 02 0131downstream0 ft. MGO - General Observation - 2 HALF MISSING TILES AT UPSTREAM SOFFIT0 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - OLD MAG COAT 10%2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS COF MISSING TILES8 ft. MGO - General Observation - TILES 100% IN PLACE22.6 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES22.6 ft. MGO - General Observation - 40% MISSING TILES27.1 ft. MGO - General Observation - 5% MISSING TILES37.8 ft. MGO - General Observation - 40% MISSING TILES55.3 ft. MGO - General Observation - 5% MISSING TILES67 ft. MGO - General Observation - 30% MISSING TILES START71.4 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR75.4 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR90.5 ft. MGO - General Observation - 30% MISSING TLES FINISH97.6 ft. MGO - General Observation - 5% MISSING TILES START109.8 ft. MGO - General Observation - 2 MISSING TILES 12:00114.1 ft. MGO - General Observation - 40% MISSING TILES126.5 ft. MGO - General Observation - 10% MISSING TILES START145.3 ft. MGO - General Observation - 255 MISSING TILES171.7 ft. MGO - General Observation - 40% NMISSING TILES START190 ft. MGO - General Observation - 5% MISSING TILES START210.2 ft. MGP - General Photograph - 20% MISSING TILED219.1 ft. MGO - General Observation - 30% MISSING TILES222.9 ft. MGO - General Observation - 5% MISSING TILES START237.8 ft. MGO - General Observation - 20% MISSING TILES249.3 ft. MGO - General Observation - 10% MISSING TILES257.6 ft. MGO - General Observation - 40% MISSING TILES265.9 ft. MGO - General Observation - 5% MISSING TILES281.9 ft. MGO - General Observation - 40% MISSING TILES START287 ft. SRC - Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR308 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG308 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES

Observation photos (19)

  • General Observation - OLD MAG COAT 10%

    2 ft. - General Observation - OLD MAG COAT 10%

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS COF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS COF MISSING TILES

  • General Observation - TILES 100% IN PLACE

    8 ft. - General Observation - TILES 100% IN PLACE

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    22.6 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - 40% MISSING TILES

    22.6 ft. - General Observation - 40% MISSING TILES

  • General Observation - 40% MISSING TILES

    37.8 ft. - General Observation - 40% MISSING TILES

  • General Observation - 30% MISSING TILES START

    67 ft. - General Observation - 30% MISSING TILES START

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    71.4 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • General Observation - 255 MISSING TILES

    145.3 ft. - General Observation - 255 MISSING TILES

  • General Observation - 40% NMISSING TILES START

    171.7 ft. - General Observation - 40% NMISSING TILES START

  • General Photograph - 20% MISSING TILED

    210.2 ft. - General Photograph - 20% MISSING TILED

  • General Observation - 30% MISSING TILES

    219.1 ft. - General Observation - 30% MISSING TILES

  • General Observation - 5% MISSING TILES START

    222.9 ft. - General Observation - 5% MISSING TILES START

  • General Observation - 20% MISSING TILES

    237.8 ft. - General Observation - 20% MISSING TILES

  • General Observation - 10% MISSING TILES

    249.3 ft. - General Observation - 10% MISSING TILES

  • General Observation - 40% MISSING TILES

    257.6 ft. - General Observation - 40% MISSING TILES

  • General Observation - 5% MISSING TILES

    265.9 ft. - General Observation - 5% MISSING TILES

  • General Observation - 40% MISSING TILES START

    281.9 ft. - General Observation - 40% MISSING TILES START

  • Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    287 ft. - Surface Reinforcement Corroded, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (34)

DistanceCodeObservation
2MGOOLD MAG COAT 10%
8MGOTILES 100% IN PLACE
27.1MGO5% MISSING TILES
71.4SRCLONG CIRCUM REBAR
75.4SRCLONG CIRCUM REBAR
287SRCCIRCUM REBAR
0MGO2 HALF MISSING TILES AT UPSTREAM SOFFIT
126.5MGO10% MISSING TILES START
249.3MGO10% MISSING TILES
22.6SAMSEVERE AGG AREAS OF MISSING TILES
190MGO5% MISSING TILES START
257.6MGO40% MISSING TILES
222.9MGO5% MISSING TILES START
145.3MGO255 MISSING TILES
37.8MGO40% MISSING TILES
109.8MGO2 MISSING TILES 12:00
308SAMSEVERE AGG
67MGO30% MISSING TILES START
171.7MGO40% NMISSING TILES START
22.6MGO40% MISSING TILES
55.3MGO5% MISSING TILES
210.2MGP20% MISSING TILED
281.9MGO40% MISSING TILES START
237.8MGO20% MISSING TILES
114.1MGO40% MISSING TILES
2SAMSEVERE AGG AREAS COF MISSING TILES
97.6MGO5% MISSING TILES START
265.9MGO5% MISSING TILES
90.5MGO30% MISSING TLES FINISH
219.1MGO30% MISSING TILES
0AMH2:55AM
0MWL
0MWM
308SAMSEVERE AGG AREAS OF MISSING TILES

Properties (4)

customer
LACSD
datetime
2022-05-17T01:37:42-07:00
documentation
MARTIN,REVELES,IGNACIO
is_lateral_inspection
false