Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2022, 09:50 AM
  • 18 0105_18 0104_04272022_040129.mp4

Date
04/27/2022
W/O
952101
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13925
Time
2:50 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10082
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_952101_TV18177_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0104
Downstream MH
18 0105
Dir. of Survey
Upstream
Length Surveyed
169.9 ft.
Total Length
169.9 ft.
Structural Index
3
Structural Quick
3F2F
Structural Rating
165
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
231
Pipe schematic from manhole 18 0104 to 18 0105
MH: 18 0104MH: 18 0105upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 01050 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN0.9 ft. MGO - General Observation - ROACHES @ MH1.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish20 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"35.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN38 ft. TS - Tap Saddle, at 09 o'clock, -, within 8 inches of joint: NO, 6"38.9 ft. MWM - Water Mark, 35 %of cross sectional area65.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"117 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"120.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start167.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start167.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start169.9 ft. MGO - General Observation - ROACHES @ MH169.9 ft. MWL - Water Level, 20 %of cross sectional area169.9 ft. MWM - Water Mark, 25 %of cross sectional area169.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED169.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED169.9 ft. AMH - Downstream Manhole, Survey Begins - 18 0104

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle, at 09 o'clock, -, within 8 inches of joint: NO, 6"

    131.9 ft. - Tap Saddle, at 09 o'clock, -, within 8 inches of joint: NO, 6"

Observations (23)

DistanceCodeObservation
167DAGS
168.4SAV
52.9TFC
0MGOROACHES @ MH
134.6TFOPEN
169.9AMH18 0105
2DAGS
0MWL
169.9MGOCONN @ MH 3 O'CLOCK/OPEN
0MWM
0MGOCONN @ MH 9 O'CLOCK/CAPPED
2SSS
104.6TFC
101.2TFA
3SAV
167SSS
131MWM
149.9TFC
169MGOROACHES @ MH
49.8TFC
0MGOCONN @ MH 3 O'CLOCK/CAPPED
131.9TS
0AMH18 0104

Properties (7)

additional_info
630074042622202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-04-27T02:50:59-07:00
documentation
PROPIPE
is_lateral_inspection
false