Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2022, 08:24 AM
  • 18 0102_18 0101_05052022_025118.mp4

Date
05/05/2022
W/O
952101
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13922
Time
1:24 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10089
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_952101_TV18177_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0102
Downstream MH
18 0101
Dir. of Survey
Downstream
Length Surveyed
225.4 ft.
Total Length
225.4 ft.
Structural Index
3
Structural Quick
413H
Structural Rating
136
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
138
Pipe schematic from manhole 18 0102 to 18 0101
MH: 18 0102MH: 18 0101downstream0 ft. MGO - General Observation - CONN @ MH 2 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 18 01020 ft. MGO - General Observation - CONN @ MH 10 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0.1 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start56.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"58.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"97.4 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES107.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"111.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"159.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"208.3 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"222.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish225.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0101225.4 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE225.4 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    97.4 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
0MGOCONN @ MH 2 O'CLOCK/ACTIVE
208.3TBC
222.2SAV
225.4AMH18 0101
2.1SAV
56.7TFC
111.2TFC
0MGOROACHES @ MH
0AMH18 0102
107.5TFC
225.4MGOCONN @ MH 3 O'CLOCK/ACTIVE
225.4MGOCONN @ MH 9 O'CLOCK/OPEN
159.9TFC
0.1MWM
0MGOCONN @ MH 10 O'CLOCK/ACTIVE
58.8TFC
210.9TFC
162.4TFC
97.4FM
0MWL

Properties (7)

additional_info
630074050422201
custom_field_three
AGGREGATE VISIBLE/FRACTURE
custom_field_two
3
customer
1
datetime
2022-05-05T01:24:53-07:00
documentation
PROPIPE
is_lateral_inspection
false