Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2022, 09:47 AM
  • 18 0092_18 0091_05022022_040516.mp4

Date
05/02/2022
W/O
952101
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13911
Time
2:47 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10086
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_952101_TV18177_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0091
Downstream MH
18 0092
Dir. of Survey
Upstream
Length Surveyed
327.6 ft.
Total Length
327.6 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
333
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
463
Pipe schematic from manhole 18 0091 to 18 0092
MH: 18 0091MH: 18 0092upstream0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 18 00920.6 ft. MGO - General Observation - ROACHES @ MH2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish90.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"150.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES176.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES225.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"232.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"267.3 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES324.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start325.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start325.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start327.6 ft. AMH - Downstream Manhole, Survey Begins - 18 0091327.6 ft. MWM - Water Mark, 35 %of cross sectional area327.6 ft. MWL - Water Level, 30 %of cross sectional area327.6 ft. MGO - General Observation - ROACHES @ MH

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    60.3 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    151.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    176.8 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
237.4TFC
325DAGS
0AMH18 0091
0MWM
230.8TFC
95.2TFC
0MWL
151.4FL
2.7SAV
176.8FL
102.5TFC
327MGOROACHES @ MH
2DAGS
325SSS
2SSS
327.6SAV
327.6AMH18 0092
60.3CL
0MGOROACHES @ MH

Properties (6)

custom_field_three
AGGREGATE VISIBLE/FRACTURE
custom_field_two
3
customer
1
datetime
2022-05-02T02:47:21-07:00
documentation
PROPIPE
is_lateral_inspection
false