Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2022, 10:20 AM
  • 18 0089_18 0088_05022022_043129.mp4

Date
05/02/2022
W/O
952101
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13908
Time
3:20 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10086
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_952101_TV18177_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0089
Downstream MH
18 0088
Dir. of Survey
Downstream
Length Surveyed
352.6 ft.
Total Length
352.6 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
347
O&M Index
2
O&M Quick
512M
O&M Rating
145
Overall Index
2
Overall Quick
Overall Rating
492
Pipe schematic from manhole 18 0089 to 18 0088
MH: 18 0089MH: 18 0088downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00890 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"159.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"170.5 ft. IG - Infiltration Gusher, from 08 to 04 o'clock, within 8 inches of joint: YES199 ft. IS - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES238.1 ft. IS - Infiltration Stain, from 12 to 04 o'clock, within 8 inches of joint: YES253.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"347.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish350 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish350 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish352 ft. MGO - General Observation - ROACHES @ MH352.5 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE352.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0088

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Gusher, from 08 to 04 o'clock, within 8 inches of joint: YES

    170.5 ft. - Infiltration Gusher, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES

    199 ft. - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 12 to 04 o'clock, within 8 inches of joint: YES

    238.1 ft. - Infiltration Stain, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
2DAGS
2SSS
0AMH18 0089
352.5MGOCONN @ MH 3 O'CLOCK/ACTIVE
253.7TFC
347.8SAV
238.1IS
0MWM
57.8TFC
159.2TFC
0MWL
0MGOROACHES @ MH
352MGOROACHES @ MH
170.5IG
352.6AMH18 0088
2.2SAV
199IS
350DAGS
350SSS

Properties (7)

additional_info
630074050222002
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-02T03:20:28-07:00
documentation
PROPIPE
is_lateral_inspection
false