Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2022, 10:35 AM
  • 18 0088_18 0087_05022022_044313.mp4

Date
05/02/2022
W/O
952101
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13907
Time
3:35 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10086
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_952101_TV18177_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0088
Downstream MH
18 0087
Dir. of Survey
Downstream
Length Surveyed
220.7 ft.
Total Length
220.7 ft.
Structural Index
3
Structural Quick
3H22
Structural Rating
133
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
140
Pipe schematic from manhole 18 0088 to 18 0087
MH: 18 0088MH: 18 0087downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00880 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. ID - Infiltration Dripper, from 09 to 10 o'clock, within 8 inches of joint: YES8.3 ft. IS - Infiltration Stain, from 08 to 11 o'clock, within 8 inches of joint: YES49.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"150.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"218 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish218 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish219.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish220.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0087

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Dripper, from 09 to 10 o'clock, within 8 inches of joint: YES

    7 ft. - Infiltration Dripper, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 08 to 11 o'clock, within 8 inches of joint: YES

    8.3 ft. - Infiltration Stain, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
0MGOROACHES @ MH
218SSS
219.4SAV
0MWM
0MWL
0AMH18 0088
2DAGS
49.2TFC
220.7AMH18 0087
218DAGS
2SSS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
8.3IS
150.5TFC
2.1SAV
7ID

Properties (7)

additional_info
630074050222002
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-05-02T03:35:42-07:00
documentation
PROPIPE
is_lateral_inspection
false