Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2022, 06:04 AM
  • 18 0085_18 0084_05052022_001529.mp4

Date
05/04/2022
W/O
952101
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13904
Time
11:04 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10089
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_952101_TV18177_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0085
Downstream MH
18 0084
Dir. of Survey
Downstream
Length Surveyed
281.4 ft.
Total Length
281.4 ft.
Structural Index
3
Structural Quick
413J
Structural Rating
282
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
282
Pipe schematic from manhole 18 0085 to 18 0084
MH: 18 0085MH: 18 0084downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00850 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start106.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"113 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES167.2 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES180.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"278.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish279 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish281 ft. MGO - General Observation - ROACHES @ MH281.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0084

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    113 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    167.2 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
0AMH18 0085
0MWL
281MGOROACHES @ MH
0MGOROACHES @ MH
2SSS
113FL
106.4TFC
0MWM
167.2FM
279SSS
2.1SAV
281.4AMH18 0084
278.5SAV
180.2TFC

Properties (7)

additional_info
630074050422201
custom_field_three
AGGREGATE VISIBLE/FRACTURE'S
custom_field_two
3
customer
1
datetime
2022-05-04T23:04:15-07:00
documentation
PROPIPE
is_lateral_inspection
false