Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2022, 05:11 AM
  • 18 0083_18 0082_05042022_233001.mp4

Date
05/04/2022
W/O
952101
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13902
Time
10:11 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10089
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_952101_TV18177_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0083
Downstream MH
18 0082
Dir. of Survey
Downstream
Length Surveyed
386 ft.
Total Length
386 ft.
Structural Index
3
Structural Quick
443O
Structural Rating
408
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
560
Pipe schematic from manhole 18 0083 to 18 0082
MH: 18 0083MH: 18 0082downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00830 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.7 ft. FM - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES15.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN36.7 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES103.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"152.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN178.7 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES202.4 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES246.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN248.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"268.5 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES283.3 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES306.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"384 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish384 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish384.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish384.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0082384.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE386 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

    5.7 ft. - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    36.7 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    178.7 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    202.4 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    268.5 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

    283.3 ft. - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
36.7FM
306.2TFA
384.3AMH18 0082
283.3FC
384.3MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWM
103.9TFA
152.2TFOPEN
178.7FM
384.2SAV
0AMH18 0083
2CM
384DAGS
5.7FM
384CM
202.4CL
0MWL
2SSS
2.1SAV
246.2TFOPEN
248.5TFC
0MGOROACHES @ MH
2DAGS
386SSS
15.8TFOPEN
268.5FM

Properties (7)

additional_info
630074050422201
custom_field_three
AGGREGATE VISIBLE/FRACTURE'S
custom_field_two
3
customer
1
datetime
2022-05-04T22:11:38-07:00
documentation
PROPIPE
is_lateral_inspection
false