Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2022, 08:43 AM
  • 18 0425_18 0076_05032022_032159.mp4

Date
05/03/2022
W/O
952101
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13893
Time
1:43 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10088
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_952101_TV18177_MAY2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0425
Downstream MH
18 0076
Dir. of Survey
Downstream
Length Surveyed
227.3 ft.
Total Length
227.3 ft.
Structural Index
3
Structural Quick
3H2F
Structural Rating
206
O&M Index
2
O&M Quick
312L
O&M Rating
131
Overall Index
2
Overall Quick
Overall Rating
337
Pipe schematic from manhole 18 0425 to 18 0076
MH: 18 0425MH: 18 0076downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 04250 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6 ft. MGO - General Observation - 60% MAG COAT6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start66 ft. ID - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES114.8 ft. IW - Infiltration Weeper, at 11 o'clock, within 8 inches of joint: YES114.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES149.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start162.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"180 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 07 to 10 o'clock, , within 8 inches of joint: YES196 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES224 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish224.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish224.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish225 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish227 ft. MGO - General Observation - ROACHES @ MH227.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0076

Observation photos (6)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    38.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES

    66 ft. - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES

  • Infiltration Weeper, at 11 o'clock, within 8 inches of joint: YES

    114.8 ft. - Infiltration Weeper, at 11 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock,  , within 8 inches of joint: YES

    114.8 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    149.3 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
196DAE
0MWL
225DAGS
6MGO60% MAG COAT
224DAE
227.3AMH18 0076
0AMH18 0425
0MWM
180DAE
227MGOROACHES @ MH
114.8IW
224.2SAV
114.8DAE
66ID
149.3DAE
162.4TFA
224.1SSS
6SAV
2DAGS
38.2SSS

Properties (7)

additional_info
630074050222202
custom_field_three
AGGREGATE VISIBLE/SPALLING
custom_field_two
3
customer
1
datetime
2022-05-03T01:43:01-07:00
documentation
PROPIPE
is_lateral_inspection
false