- Date
- 04/08/2022
- W/O
- 946842
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00577
- PipeID
- P26095
- Time
- 3:32 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K10033
- Sewer Name
- 14 TRUNK "A"
- City
- LANCASTER
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 14
- Page No.
- 06
- Purpose
- Routine Assessment
- Project
- RFIR_WO_946842_TV14039_APR2022
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- 14 0046
- Downstream MH
- 14 1129
- Dir. of Survey
- Downstream
- Length Surveyed
- 340.1 ft.
- Total Length
- 340.1 ft.
- Structural Index
- 4
- Structural Quick
- 5131
- Structural Rating
- 8
- O&M Index
- 3
- O&M Quick
- 4121
- O&M Rating
- 6
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 14
Pipe schematic from manhole 14 0046 to 14 1129 Observation photos (4)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

4 ft. - General Observation - MAG COAT

4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start