Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2022, 07:57 AM
  • 15 0108_15 0107_03222022_010901.mp4

Date
03/22/2022
W/O
941492
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00590
PipeID
P11986
Time
12:57 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9931
Sewer Name
15 ABBEY STREET TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_941492_TV15245_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0108
Downstream MH
15 0107
Dir. of Survey
Downstream
Length Surveyed
158.9 ft.
Total Length
158.9 ft.
Structural Index
3
Structural Quick
4438
Structural Rating
52
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
52
Pipe schematic from manhole 15 0108 to 15 0107
MH: 15 0108MH: 15 0107downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01088.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES11.6 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES16.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish40.5 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start57.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.5 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish76.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES78.9 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES82.8 ft. CS - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES110.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start110.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - CONNECTION "PASSED-BY" DURING SURVEY.126.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish126.9 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES - FRACTURE POSSIBLY CONTINUES FROM 5 O'CLOCK TO 8 O'CLOCK.139.3 ft. FC - Fracture Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES158.9 ft. MGO - General Observation - CONNECTION AT THE MH 12 OC'LOCK158.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0107

Observation photos (9)

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    11.6 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    40.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    57.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    76.5 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    78.9 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    82.8 ft. - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    110.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES

    139.3 ft. - Fracture Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
139.3FC
8.7CL
57.5FM
158.9MGOCONNECTION AT THE MH 12 OC'LOCK
76.5CL
16.3CM
40.5CM
126.9CM
126.9FMFRACTURE POSSIBLY CONTINUES FROM 5 O'CLOCK TO 8 O'CLOCK.
0MGOCONNECTION AT THE MH 3 OC'LOCK
57.3TB
0MWM
82.8CS
78.9CS
110.4CM
11.6CL
158.9AMH15 0107
40.5FM
0MWL
110.8TFCONNECTION "PASSED-BY" DURING SURVEY.
0AMH15 0108

Properties (7)

additional_info
630074032122202
custom_field_three
CRACKS/ FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-03-22T00:57:35-07:00
documentation
PROPIPE
is_lateral_inspection
false