- Date
- 03/22/2022
- W/O
- 941492
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00590
- PipeID
- P11984
- Time
- 12:29 AM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9931
- Sewer Name
- 15 ABBEY STREET TRUNK
- City
- LA PUENTE
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 38
- Purpose
- Routine Assessment
- Project
- RFIR_WO_941492_TV15245_MAR2022
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 10 in.
- Width
- 10 in.
- Upstream MH
- 15 0106
- Downstream MH
- 15 0105
- Dir. of Survey
- Downstream
- Length Surveyed
- 223.1 ft.
- Total Length
- 223.1 ft.
- Structural Index
- 3
- Structural Quick
- 423F
- Structural Rating
- 111
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 111
Pipe schematic from manhole 15 0106 to 15 0105 Observation photos (5)

9 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

14.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

44.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

83.8 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

93.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start