Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2022, 08:23 AM
  • 22 0480_22 0479_04142022_013646.mp4

Date
04/14/2022
W/O
946708
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00800
PipeID
P16819
Time
1:23 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9963
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_946708_TV22031_APR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0480
Downstream MH
22 0479
Dir. of Survey
Downstream
Length Surveyed
299.4 ft.
Total Length
299.4 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 22 0480 to 22 0479
MH: 22 0480MH: 22 0479downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 04800 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"10.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"15.6 ft. MGO - General Observation - MAG COAT52.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"55.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"103.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"106.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"132.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES145.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"148.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"199.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"202.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"250.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"254.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"298.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish299.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0479

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    15.6 ft. - General Observation - MAG COAT

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    132.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
52.3TFC
299.4AMH22 0479
103.9TF
0AMH22 0480
0MWM
202.7TFC
132.3FM
55.2TFC
10.4TFC
254.2TFC
250.9TF
0MWL
2SAP
298.9SAP
15.6MGOMAG COAT
7.1TF
106.9TFC
145.9TF
148.7TFC
199.6TFC

Properties (7)

additional_info
630138041322201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-04-14T01:23:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false