Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2022, 06:51 AM
  • 08 0150_08 0677_04152022_000123.mp4

Date
04/14/2022
W/O
947156
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00446
PipeID
P24641
Time
11:51 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10071
Sewer Name
08 FIGUEROA STREET RELIEF TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
01
Purpose
Routine Assessment
Project
WO_947156_TV08016_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0677
Downstream MH
08 0150
Dir. of Survey
Upstream
Length Surveyed
67.6 ft.
Total Length
67.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312B
O&M Rating
29
Overall Index
2
Overall Quick
Overall Rating
29
Pipe schematic from manhole 08 0677 to 08 0150
MH: 08 0677MH: 08 0150upstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Ends - 08 01500 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish13.8 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES65.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start67.6 ft. MWM - Water Mark, 15 %of cross sectional area67.6 ft. MWL - Water Level, 10 %of cross sectional area67.6 ft. AMH - Downstream Manhole, Survey Begins - 08 0677

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  15 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES

    53.8 ft. - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
53.8DSZ
0MWM
67.6MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
67.6AMH08 0150
67.6MGOCONNECTION AT THE MH 3 OC'LOCK
2.2DAE
67.6DAE
0AMH08 0677

Properties (8)

additional_info
630074041422201
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2022-04-14T23:51:44-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
37470