Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2022, 10:31 AM
  • 08 0672_08 0671_04142022_034311.mp4

Date
04/14/2022
W/O
947156
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00446
PipeID
P24635
Time
3:31 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10070
Sewer Name
08 FIGUEROA STREET RELIEF TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_947156_TV08016_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0672
Downstream MH
08 0671
Dir. of Survey
Downstream
Length Surveyed
411.1 ft.
Total Length
411.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2O00
O&M Rating
162
Overall Index
2
Overall Quick
Overall Rating
165
Pipe schematic from manhole 08 0672 to 08 0671
MH: 08 0672MH: 08 0671downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 06720 ft. MWL - Water Level, 10 %of cross sectional area3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start194.8 ft. LFBU - Lining Failure Bulges, at 12 o'clock, within 8 inches of joint: NO408.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish411.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0671

Observation photos (1)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
194.8LFBU
411.1AMH08 0671
0MWM
408.7DAE
0AMH08 0672
0MWL
3DAE

Properties (8)

additional_info
630074041322203
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2022-04-14T03:31:30-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
37470