Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2022, 08:19 AM
  • 08 0664_08 0663_04152022_012615.mp4

Date
04/15/2022
W/O
947156
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00446
PipeID
P24627
Time
1:19 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10071
Sewer Name
08 FIGUEROA STREET RELIEF TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
WO_947156_TV08016_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0663
Downstream MH
08 0664
Dir. of Survey
Upstream
Length Surveyed
289.7 ft.
Total Length
289.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2V00
O&M Rating
226
Overall Index
2
Overall Quick
Overall Rating
226
Pipe schematic from manhole 08 0663 to 08 0664
MH: 08 0663MH: 08 0664upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 06640.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish3.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: NO, Finish283.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: NO, Start286.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start289.6 ft. MWM - Water Mark, 15 %of cross sectional area289.7 ft. AMH - Downstream Manhole, Survey Begins - 08 0663289.7 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMH08 0663
6DAGS
289.6DAE
286DAGS
0.1MWM
289.7AMH08 0664
3DAE
0MWL

Properties (8)

additional_info
630074041422201
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2022-04-15T01:19:45-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
37470