Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2022, 10:25 AM
  • 15 1095_15 1094_04142022_034431.mp4

Date
04/14/2022
W/O
947050
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00614
PipeID
P12855
Time
3:25 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9965
Sewer Name
15 MERCED TRUNK, SECTION 1
City
S EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_947050_TV15099_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 1095
Downstream MH
15 1094
Dir. of Survey
Downstream
Length Surveyed
322 ft.
Total Length
322 ft.
Structural Index
3
Structural Quick
4121
Structural Rating
6
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 15 1095 to 15 1094
MH: 15 1095MH: 15 1094downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 10952 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start6.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"23 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES61.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"101.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"112.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"123.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"221.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"252.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"309 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"309 ft. FM - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: NO322 ft. MGO - General Observation - GIS MAPS CALL FOR 320'322 ft. AMH - Downstream Manhole, Survey Ends - 15 1094322 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    23 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    112.1 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    309 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: NO

    309 ft. - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: NO

Observations (18)

DistanceCodeObservation
221.8TF
322MGOGIS MAPS CALL FOR 320'
309TBC
23CL
0MGOCONNECTION AT MH 9 O'CLOCK
322AMH15 1094
252.8TF
0MWL
6.1TFC
123.1TF
61.5TFC
0MWM
309FM
101.3TFC
2DAGS
0AMH15 1095
322DAGS
112.1TB

Properties (7)

additional_info
630138041322203
custom_field_three
FRACTURE, CRACK
custom_field_two
3
customer
1
datetime
2022-04-14T03:25:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false