- Date
- 04/12/2022
- W/O
- 946964
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00501
- PipeID
- P07143
- Time
- 10:05 PM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K10064
- Sewer Name
- 05 PALOS VERDES NORTH SLOPE TRUNK, SECT 1
- City
- TORRANCE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 35
- Purpose
- Routine Assessment
- Project
- RFIR_WO_946964_TV05088_APR2022
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 21 in.
- Upstream MH
- 05 1915
- Downstream MH
- 05 1916
- Dir. of Survey
- Upstream
- Length Surveyed
- 384.8 ft.
- Total Length
- 384.8 ft.
- Structural Index
- 3
- Structural Quick
- 433N
- Structural Rating
- 240
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 240
Pipe schematic from manhole 05 1915 to 05 1916 Observation photos (5)

2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

9.7 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

41.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

55.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

139.2 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES