Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2022, 10:37 AM
  • 01 1178_01 1177_04062022_035428.mp4

Date
04/06/2022
W/O
946843
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00225
PipeID
P02032
Time
3:37 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9792
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
WO_946843_TV01072_APR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
01 1178
Downstream MH
01 1177
Dir. of Survey
Downstream
Length Surveyed
269.5 ft.
Total Length
269.5 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
162
O&M Index
2
O&M Quick
412J
O&M Rating
110
Overall Index
3
Overall Quick
Overall Rating
272
Pipe schematic from manhole 01 1178 to 01 1177
MH: 01 1178MH: 01 1177downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11780 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"30.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"56.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"59.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"91.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"101.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"162.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"168.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"206.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"206.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: NO211.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"256.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"267.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish267.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish269.5 ft. AMH - Downstream Manhole, Survey Ends - 01 1177269.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: NO

    206.6 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: NO

Observations (22)

DistanceCodeObservation
267.9SAP
0MWL
267.9DAGS
2.1DAGS
0AMH01 1178
101.7TF
30.7TF
56.1TF
0MWM
269.5AMH01 1177
162.9TF
206.6FL
0MGOCONNECTION AT THE MH 9 OC'LOCK
2.1SAP
256.9TF
211.6TF
206.5TF
168.3TF
91.7TF
269.5MGOCONNECTION AT THE MH 3 OC'LOCK
10.7TFA
59.2TB

Properties (7)

additional_info
6300630406222021
custom_field_three
FRACTURES, AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2022-04-06T03:37:00-07:00
documentation
PROPIPE
is_lateral_inspection
false