Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2022, 11:06 AM
  • 01 1176B_01 1176A_04062022_042004.mp4

Date
04/06/2022
W/O
946843
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00225
PipeID
P02030
Time
4:06 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9792
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
WO_946843_TV01072_APR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
01 1176B
Downstream MH
01 1176A
Dir. of Survey
Downstream
Length Surveyed
143.2 ft.
Total Length
143.2 ft.
Structural Index
3
Structural Quick
413E
Structural Rating
91
O&M Index
2
O&M Quick
412E
O&M Rating
60
Overall Index
3
Overall Quick
Overall Rating
151
Pipe schematic from manhole 01 1176B to 01 1176A
MH: 01 1176BMH: 01 1176Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 1176B0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"10.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"37.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES66.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"69 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES69 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"89.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"115.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"135.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"138 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"141.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish141.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish143.2 ft. AMH - Downstream Manhole, Survey Ends - 01 1176A143.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    37.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    69 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
2SAP
0MWL
115.2TF
141.5SAP
69FM
0AMH01 1176B
37.6CM
8TF
89.6TFC
66.4TF
0MWM
69TF
2DAGS
138TF
135.4TF
141.5DAGS
10.3TF
143.2AMH01 1176A
143.2MGOCONNECTION AT THE MH 3 OC'LOCK

Properties (7)

additional_info
6300630406222021
custom_field_three
FRACTURES, AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2022-04-06T04:06:51-07:00
documentation
PROPIPE
is_lateral_inspection
false