Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2022, 07:47 AM
  • 01 1174A_01 1174_04082022_010804.mp4

Date
04/08/2022
W/O
946843
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00225
PipeID
P02026
Time
12:47 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9794
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
WO_946843_TV01072_APR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
01 1174A
Downstream MH
01 1174
Dir. of Survey
Downstream
Length Surveyed
258.5 ft.
Total Length
258.5 ft.
Structural Index
3
Structural Quick
413J
Structural Rating
163
O&M Index
2
O&M Quick
2I00
O&M Rating
98
Overall Index
3
Overall Quick
Overall Rating
261
Pipe schematic from manhole 01 1174A to 01 1174
MH: 01 1174AMH: 01 1174downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 1174A0 ft. MWM - Water Mark, 40 %of cross sectional area2.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20 ft. MGO - General Observation - MAG COATING21.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start34.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"42.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 01 to 03 o'clock, , within 8 inches of joint: NO44.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO44.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"59.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"104 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO105.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 4"120.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"132.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"168.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"170.1 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES183.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"218.5 ft. DAR - Deposits Attached Ragging, 10 %of cross sectional area, at 10 o'clock, , within 8 inches of joint: NO218.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"254.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"256.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish256.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish258.5 ft. AMH - Downstream Manhole, Survey Ends - 01 1174

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    21.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 01 to 03 o'clock,  , within 8 inches of joint: NO

    42.9 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 01 to 03 o'clock, , within 8 inches of joint: NO

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO

    44.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO

    104 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    170.1 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Ragging, 10 %of cross sectional area, at 10 o'clock,  , within 8 inches of joint: NO

    218.5 ft. - Deposits Attached Ragging, 10 %of cross sectional area, at 10 o'clock, , within 8 inches of joint: NO

Observations (25)

DistanceCodeObservation
105.1TFA
59.8TF
218.6TF
132.7TF
44.5FL
42.9DAGS
170.1FM
258.5AMH01 1174
256.7SAP
168.7TF
104FL
21.8DAGS
183.4TF
254.8TF
0MGOCONNECTION AT THE MH 3 OC'LOCK
2.3SAP
120.3TF
0MWL
34.4TF
0AMH01 1174A
0MWM
218.5DAR
256.7DAGS
20MGOMAG COATING
44.5TF

Properties (7)

additional_info
630074040722201
custom_field_three
FRACTURES, AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2022-04-08T00:47:21-07:00
documentation
PROPIPE
is_lateral_inspection
false