- Date
- 04/08/2022
- W/O
- 946843
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00225
- PipeID
- P02025
- Time
- 1:46 AM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K9794
- Sewer Name
- 01 WILCOX AVENUE TRUNK
- City
- BELL
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 08
- Purpose
- Routine Assessment
- Project
- WO_946843_TV01072_APR2022
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 24 in.
- Upstream MH
- 01 1174
- Downstream MH
- 01 1173
- Dir. of Survey
- Downstream
- Length Surveyed
- 356.3 ft.
- Total Length
- 356.3 ft.
- Structural Index
- 3
- Structural Quick
- 3M22
- Structural Rating
- 220
- O&M Index
- 2
- O&M Quick
- 2M00
- O&M Rating
- 140
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 360
Pipe schematic from manhole 01 1174 to 01 1173 Observation photos (5)

2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

120 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

208.1 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: NO