Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2022, 06:46 AM
  • 15 1122_15 1121_03222022_235827.mp4

Date
03/22/2022
W/O
941337
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00615
PipeID
P12882
Time
11:46 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9934
Sewer Name
15 MERCED TRUNK, SECTION 2
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_941337_TV15100_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 1122
Downstream MH
15 1121
Dir. of Survey
Downstream
Length Surveyed
216.7 ft.
Total Length
216.7 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 15 1122 to 15 1121
MH: 15 1122MH: 15 1121downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 112210.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"18.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"25.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"26.7 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"28.2 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"42.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"70.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES86.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"108.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK216.6 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK216.7 ft. AMH - Downstream Manhole, Survey Ends - 15 1121

Observation photos (5)

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    25.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    26.7 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    28.2 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    70.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    108.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (19)

DistanceCodeObservation
162.3TF
70.6CL
86.7TFC
108.3TFC
54.1TF
10.2TF
42.6TF
216.6MGOCONNECTION AT THE MH 9 OC'LOCK
25.2TB
216.7AMH15 1121
0MWL
0MWM
0AMH15 1122
197.9TF
216.6MGOCONNECTION AT THE MH 3 OC'LOCK
28.2TB
18.2TF
119.4TF
26.7TB

Properties (7)

additional_info
630074032222201
custom_field_three
RFIR NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2022-03-22T23:46:57-07:00
documentation
PROPIPE
is_lateral_inspection
false