Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2022, 06:58 AM
  • 18 0059_18 0058_03242022_001233.mp4

Date
03/23/2022
W/O
946713
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00689
PipeID
P13873
Time
11:58 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9937
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_946713_TV18176_APR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0059
Downstream MH
18 0058
Dir. of Survey
Downstream
Length Surveyed
321.3 ft.
Total Length
321.3 ft.
Structural Index
3
Structural Quick
413L
Structural Rating
195
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
195
Pipe schematic from manhole 18 0059 to 18 0058
MH: 18 0059MH: 18 0058downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 18 00592.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4 ft. FM - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES29.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.4 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES114.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"120.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"305.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"319 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0058

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    4 ft. - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

    79.4 ft. - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
141.6TF
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
114.4TF
321.3AMH18 0058
29.3TF
120.6TF
0MWM
4FM
0MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
2.4SAV
305.7TF
232.8TF
79.4FC
281.5TF
319SAV
205.9TF
0AMH18 0059
278.2TF
211.7TF

Properties (7)

additional_info
630074032322062
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-03-23T23:58:09-07:00
documentation
PROPIPE
is_lateral_inspection
false