Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2022, 09:37 AM
  • 18 0041_18 0040_03242022_024747.mp4

Date
03/24/2022
W/O
946713
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00689
PipeID
P13856
Time
2:37 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9937
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_946713_TV18176_APR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0041
Downstream MH
18 0040
Dir. of Survey
Downstream
Length Surveyed
243.8 ft.
Total Length
243.8 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
144
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
144
Pipe schematic from manhole 18 0041 to 18 0040
MH: 18 0041MH: 18 0040downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00410 ft. MWL - Water Level, 5 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"29.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"63.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"208.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish243.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK243.8 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK243.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0040

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
69.3TFC
0MWM
0AMH18 0041
243.8SAV
151.1TFC
63.2TFC
2.3SAV
141.9TFC
0MWL
29.9TFC
208.6TFC
243.8MGOCONNECTION AT THE MH 3 OC'LOCK
243.8MGOCONNECTION AT THE MH 9 OC'LOCK
243.8AMH18 0040
23.8TFC

Properties (7)

additional_info
630074032322062
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-03-24T02:37:21-07:00
documentation
PROPIPE
is_lateral_inspection
false