Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2022, 07:15 AM
  • 15 0136_15 0135_03232022_002609.mp4

Date
03/23/2022
W/O
941456
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12035
Time
12:15 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10016
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_941456_TV15037_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0136
Downstream MH
15 0135
Dir. of Survey
Downstream
Length Surveyed
72.1 ft.
Total Length
72.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 15 0136 to 15 0135
MH: 15 0136MH: 15 0135downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 01362 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start72.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish72.1 ft. MSA - Survey Abandoned - DUE TO GREASE/SLUDGE72.1 ft. DAGS - Deposits Attached Grease, 30 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - GREASE/SLUDGE72.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (4)

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Survey Abandoned - DUE TO GREASE/SLUDGE

    72.1 ft. - Survey Abandoned - DUE TO GREASE/SLUDGE

  • Deposits Attached Grease, 30 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES - GREASE/SLUDGE

    72.1 ft. - Deposits Attached Grease, 30 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - GREASE/SLUDGE

Observations (10)

DistanceCodeObservation
72.1SAP
0MWL
0MWM
2DAGS
0MGOCONNECTION AT MH 6 O'CLOCK
72.1MSADUE TO GREASE/SLUDGE
2SAP
72.1DAGSGREASE/SLUDGE
0AMH15 0136
72.1DAGS

Properties (7)

additional_info
630138032222201
custom_field_three
ABANDONED DUE TO GREASE/SLUDGE
custom_field_two
5
customer
1
datetime
2022-03-23T00:15:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false