Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2022, 07:40 AM
  • 15 0142_15 0141A_03242022_010855.mp4

Date
03/24/2022
W/O
941456
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12042
Time
12:40 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10017
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_941456_TV15037_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0142
Downstream MH
15 0141A
Dir. of Survey
Downstream
Length Surveyed
375.6 ft.
Total Length
375.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 15 0142 to 15 0141A
MH: 15 0142MH: 15 0141Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01420 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT114.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"223.9 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"227 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"247.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"373.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish375.6 ft. MGO - General Observation - COCKROACHES IN MH375.6 ft. MGO - General Observation - CONNECTION AT MH 3, 9 O'CLOCK375.6 ft. AMH - Downstream Manhole, Survey Ends - 15 0141A

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • General Observation - COCKROACHES IN MH

    375.6 ft. - General Observation - COCKROACHES IN MH

Observations (14)

DistanceCodeObservation
0MWL
0AMH15 0142
0MWM
247.6TF
375.6MGOCOCKROACHES IN MH
373.7DAGS
227TBA
375.6MGOCONNECTION AT MH 3, 9 O'CLOCK
2DAGS
223.9TB
2MGOMAG COAT
0MGOCONNECTION AT MH 3 O'CLOCK
114.1TFA
375.6AMH15 0141A

Properties (7)

additional_info
630138032322201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2022-03-24T00:40:47-07:00
documentation
PRO PIPE
is_lateral_inspection
false