Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2022, 06:52 AM
  • 15 0139_15 0138_03242022_000607.mp4

Date
03/23/2022
W/O
941456
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12038
Time
11:52 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10017
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_941456_TV15037_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0138
Downstream MH
15 0139
Dir. of Survey
Upstream
Length Surveyed
316.5 ft.
Total Length
316.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 15 0138 to 15 0139
MH: 15 0138MH: 15 0139upstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Ends - 15 01391.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish67.3 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"93.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"170.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"227.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"237 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"314.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start314.5 ft. MGO - General Observation - MAG COAT316.5 ft. AMH - Downstream Manhole, Survey Begins - 15 0138316.5 ft. MWL - Water Level, 10 %of cross sectional area316.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK316.5 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    316.5 ft. - General Observation - COCKROACHES IN MH

Observations (15)

DistanceCodeObservation
0AMH15 0138
222.8TFC
145.8TBA
79.5TFA
316.5MGOCONNECTION AT MH 3 O'CLOCK
88.6TFC
316.5MGOCOCKROACHES IN MH
0MWL
249.2TBA
2DAGS
0MGOCONNECTION AT MH 3 O'CLOCK
316.5AMH15 0139
2MGOMAG COAT
0MWM
314.6DAGS

Properties (7)

additional_info
630138032322201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2022-03-23T23:52:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false