Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2022, 06:41 AM
  • 15 0138_15 0137_03232022_235158.mp4

Date
03/23/2022
W/O
941456
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12037
Time
11:41 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10017
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_941456_TV15037_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Square
Height
15 in.
Width
15 in.
Upstream MH
15 0137
Downstream MH
15 0138
Dir. of Survey
Upstream
Length Surveyed
293.3 ft.
Total Length
293.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 15 0137 to 15 0138
MH: 15 0137MH: 15 0138upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 01380 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish26.9 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 6", 1"79.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"228 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"291.1 ft. MGO - General Observation - MAG COAT291.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start293.3 ft. MWL - Water Level, 10 %of cross sectional area293.3 ft. MWM - Water Mark, 15 %of cross sectional area293.3 ft. AMH - Downstream Manhole, Survey Begins - 15 0137

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2.2 ft. - General Observation - MAG COAT

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    266.4 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

Observations (11)

DistanceCodeObservation
65.3TFA
0MWL
2DAGS
293.3AMH15 0138
0MWM
290.2DAGS
293.3MGOCONNECTION AT MH 3 O'CLOCK
0AMH15 0137
214.1TFA
266.4TBI
2.2MGOMAG COAT

Properties (7)

additional_info
630138032322201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2022-03-23T23:41:02-07:00
documentation
PRO PIPE
is_lateral_inspection
false