Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2022, 09:20 AM
  • 15 0125_15 0124_03232022_023107.mp4

Date
03/23/2022
W/O
941456
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12024
Time
2:20 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10016
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_941456_TV15037_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0125
Downstream MH
15 0124
Dir. of Survey
Downstream
Length Surveyed
257.7 ft.
Total Length
257.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0125 to 15 0124
MH: 15 0125MH: 15 0124downstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01252 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start130.1 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"151 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish255.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish257.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK257.7 ft. MGO - General Observation - COCKROACHES IN MH257.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0124

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    257.7 ft. - General Observation - COCKROACHES IN MH

Observations (15)

DistanceCodeObservation
0MGOCOCKROACHES IN MH
257.7MGOCONNECTION AT MH 3 O'CLOCK
2DAGS
257.7MGOCOCKROACHES IN MH
151TF
0MWM
130.1TB
0MWL
0AMH15 0125
2.4SAP
154.1TF
257.7AMH15 0124
199.9TFC
255.5DAGS
255.5SAP

Properties (5)

additional_info
630138032222201
customer
1
datetime
2022-03-23T02:20:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false