Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2022, 06:56 AM
  • 15 0121_15 0158_03252022_000206.mp4

Date
03/24/2022
W/O
941456
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12019
Time
11:56 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10018
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_941456_TV15037_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0121
Downstream MH
15 0158
Dir. of Survey
Downstream
Length Surveyed
94.9 ft.
Total Length
95 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0121 to 15 0158
MH: 15 0121MH: 15 0158downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01212 ft. MGO - General Observation - MAG COAT5.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"6.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"57.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish95 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK95 ft. MGO - General Observation - STOP LOG AT D/S CONNECTION95 ft. AMH - Downstream Manhole, Survey Ends - 15 0158

Observation photos (2)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
95MGOCONNECTION AT MH 3 O'CLOCK
5.6TFA
0MWL
2MGOMAG COAT
6.2SAP
95MGOSTOP LOG AT D/S CONNECTION
95AMH15 0158
0MWM
36.4TF
57.2TFC
0AMH15 0121
93.1SAP

Properties (5)

additional_info
630138032422201
customer
1
datetime
2022-03-24T23:56:03-07:00
documentation
PRO PIPE
is_lateral_inspection
false