Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2022, 09:35 AM
  • 15 0120_15 0119_03242022_025203.mp4

Date
03/24/2022
W/O
941456
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12017
Time
2:35 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10017
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_941456_TV15037_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0119
Downstream MH
15 0120
Dir. of Survey
Upstream
Length Surveyed
378 ft.
Total Length
378.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0119 to 15 0120
MH: 15 0119MH: 15 0120upstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Ends - 15 01200 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish2.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish82.3 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"148.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"192.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"240.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"246.1 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"289.5 ft. MGO - General Observation - MAG COAT292.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"301.7 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"322.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"376.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start376.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start378.1 ft. MWL - Water Level, 5 %of cross sectional area378.1 ft. AMH - Downstream Manhole, Survey Begins - 15 0119378.1 ft. MWM - Water Mark, 10 %of cross sectional area

Observation photos (4)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    88.6 ft. - General Observation - MAG COAT

  • General Observation - COCKROACHES IN MH

    378.1 ft. - General Observation - COCKROACHES IN MH

Observations (20)

DistanceCodeObservation
185.9TFC
137.3TFA
375.8DAGS
378.1MGOCOCKROACHES IN MH
295.8TBA
229.3TFC
2SAV
378.1AMH15 0120
0MWL
0AMH15 0119
85.9TFA
132TFA
378.1MGOCONNECTION AT MH 3 O'CLOCK
76.4TBA
88.6MGOMAG COAT
0MWM
375.8SAV
2DAGS
219.8TFA
55.3TFC

Properties (7)

additional_info
630138032322201
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2022-03-24T02:35:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false