Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2022, 10:21 AM
  • 15 0119_15 0118_03242022_033454.mp4

Date
03/24/2022
W/O
941456
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00634
PipeID
P12016
Time
3:21 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10017
Sewer Name
15 TYLER AVENUE TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_941456_TV15037_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0119
Downstream MH
15 0118
Dir. of Survey
Downstream
Length Surveyed
375.1 ft.
Total Length
375.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0119 to 15 0118
MH: 15 0119MH: 15 0118downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01192 ft. MGO - General Observation - MAG COAT9.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"24.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"73.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"94.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"158.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start219.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"222.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"225.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"267.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"350.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"362.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"372.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish375.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0118

Observation photos (2)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    158.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
375.1AMH15 0118
94.5TFA
158.3SAV
0MWL
350.3TFA
146.3TF
225.7TFA
73.4TF
222.4TFA
0MWM
24.3TFA
267.7TFC
9.3TF
2MGOMAG COAT
362.5TFA
219.2TFA
0AMH15 0119
372.8SAV

Properties (7)

additional_info
630138032322201
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2022-03-24T03:21:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false