Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2022, 08:35 AM
  • 01 0093_01 0092_04132022_022919.mp4

Date
04/13/2022
W/O
946705
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00762
Time
1:35 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10067
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_946705_TV01254_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0093
Downstream MH
01 0092
Dir. of Survey
Downstream
Length Surveyed
335.1 ft.
Total Length
335.1 ft.
Structural Index
3
Structural Quick
4K3L
Structural Rating
446
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
450
Pipe schematic from manhole 01 0093 to 01 0092
MH: 01 0093MH: 01 0092downstream0 ft. MGO - General Observation - CONN @ MH 8 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00930 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start27 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES34.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start93.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN211.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - CRACKED CONN/15% ROOTS-LATERAL262.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"333 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish333.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish335.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0092335.1 ft. MGO - General Observation - ROACHES @ MH335.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN335.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    27 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    34.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
34.1FM
142.6TFOPEN
333SSS
333.4FM
0MGOCONN @ MH 8 O'CLOCK/ACTIVE
2CM
0MWM
335.1AMH01 0092
93.9TFC
0MWL
262.4TFC
0AMH01 0093
211.4TFACRACKED CONN/15% ROOTS-LATERAL
27FM
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
335.1MGOROACHES @ MH
335.1MGOCONN @ MH 3 O'CLOCK/OPEN
333CM
333DAGS
2SSS
2DAGS
0MGOROACHES @ MH
335.1MGOCONN @ MH 9 O'CLOCK/ACTIVE

Properties (7)

additional_info
630074041222205
custom_field_three
MULTIPLE CONTINUOUS FRACTRUES
custom_field_two
2
customer
1
datetime
2022-04-13T01:35:26-07:00
documentation
PROPIPE
is_lateral_inspection
false