Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2022, 09:08 AM
  • 01 0056_01 0055_04142022_022431.mp4

Date
04/14/2022
W/O
946705
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00725
Time
2:08 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10069
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_946705_TV01254_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
01 0056
Downstream MH
01 0055
Dir. of Survey
Downstream
Length Surveyed
350.8 ft.
Total Length
350.8 ft.
Structural Index
3
Structural Quick
4M3M
Structural Rating
629
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
767
Pipe schematic from manhole 01 0056 to 01 0055
MH: 01 0056MH: 01 0055downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 01 00560 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start76 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"78.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"114 ft. FM - Fracture Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES124.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"128.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"130.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"176.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.1 ft. B - Broken, from 11 to 01 o'clock, within 8 inches of joint: YES225.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"280.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"329.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"332.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"348 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish348.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish350.7 ft. MGO - General Observation - CONN @ MH 3 OCLOCK/OPEN350.8 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED350.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0055

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"

    124.4 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"

Observations (32)

DistanceCodeObservation
0MGOROACHES @ MH
179.5TFC
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
0AMH01 0056
348CM
130.6TFC
348.3FM
128.1TFC
0MWL
225.4TFC
277.5TFC
176.4TFC
332.6TFC
2DAGS
329.7TFC
348SSS
228.3TFC
114FM
3.5FM
350.7MGOCONN @ MH 3 OCLOCK/OPEN
2SSS
350.8MGOCONN @ MH 9 O'CLOCK/CAPPED
78.6TFC
0MWM
124.4TBA
76TFC
191.1B
2CM
350.8AMH01 0055
348DAGS
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
280.6TFC

Properties (7)

additional_info
630074041322202
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2022-04-14T02:08:23-07:00
documentation
PROPIPE