Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2022, 11:02 AM
  • B 0622_B 0621_4132022_040832.mp4

Date
04/13/2022
W/O
0941294
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00107
PipeID
P09287
Time
4:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3063
Sewer Name
B JOINT OUTFALL B - UNIT 8D
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20220413MDM_JOINT_OUTFALL_B_UNIT_8D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
B 0622
Downstream MH
B 0621
Dir. of Survey
Downstream
Length Surveyed
416.8 ft.
Total Length
416.8 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole B 0622 to B 0621
MH: B 0622MH: B 0621downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - MAG COAT 95%0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped0 ft. AMH - Upstream Manhole, Survey Begins - 4:05AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT50 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE125.7 ft. MGP - General Photograph317.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCREE UNDER MAG COAT416 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT416 ft. MGO - General Observation - MAG COAT 95%416 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active416.8 ft. AMH - Downstream Manhole, Survey Ends - 4:35AM

Observation photos (5)

  • General Observation - MAG COAT 95%

    0 ft. - General Observation - MAG COAT 95%

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    50 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • General Photograph

    125.7 ft. - General Photograph

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCREE UNDER MAG COAT

    317.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCREE UNDER MAG COAT

Observations (14)

DistanceCodeObservation
416.8AMH4:35AM
416SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0MGOConn. @ Mh, 3 O' Clock. Active
0MWM
0MWL
0MGOMAG COAT 95%
317.2SSSBLISTERING PEELING CONCREE UNDER MAG COAT
50SSSBLISTERING PEELING CONCRETE
0MGOConn. @ Mh, 9 O' Clock. Capped
125.7MGP
416MGOMAG COAT 95%
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
416MGOConn. @ Mh, 3 O' Clock. Active
0AMH4:05AM

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE UNDER 95% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2022-04-13T04:02:20-07:00
documentation
MARTIN,IGNACIO
is_lateral_inspection
false