Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2022, 04:27 PM
  • A 0615_A 0614_02162022_084502.mp4

Date
02/16/2022
W/O
936573
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07820
Time
8:27 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9905
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
24
Purpose
Routine Assessment
Project
WO_936573_TV21027_FEB2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
51 in.
Upstream MH
A 0615
Downstream MH
A 0614
Dir. of Survey
Downstream
Length Surveyed
580.7 ft.
Total Length
580.7 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole A 0615 to A 0614
MH: A 0615MH: A 0614downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 06150 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. MGO - General Observation - MAG COATING3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start525.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"568.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start577 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO579 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish580.7 ft. AMH - Downstream Manhole, Survey Ends - A 0614

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    568.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

    577 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
579SAP
0MWL
3SSS
525.3TFC
568.3SAP
580.7AMHA 0614
2.1MGOMAG COATING
0AMHA 0615
0MWM
577SRV

Properties (7)

additional_info
630098021622051
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE/SPALLIN
custom_field_two
2
customer
1
datetime
2022-02-16T08:27:48-08:00
documentation
PROPIPE
is_lateral_inspection
false