Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2022, 07:00 PM
  • A 0665_A 0664_02102022_112935.mp4

Date
02/10/2022
W/O
936573
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07874
Time
11:00 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9902
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Routine Assessment
Project
WO_936573_TV21027_FEB2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
36 in.
Upstream MH
A 0665
Downstream MH
A 0664
Dir. of Survey
Downstream
Length Surveyed
1000.4 ft.
Total Length
1000.4 ft.
Structural Index
2
Structural Quick
3R2f
Structural Rating
683
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
683
Pipe schematic from manhole A 0665 to A 0664
MH: A 0665MH: A 0664downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 06650 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. MGO - General Observation - MAG COATING THROUGHOUT20 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start184.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"513.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start649.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"994 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"998 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish998.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1000.4 ft. AMH - Downstream Manhole, Survey Ends - A 0664

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    513.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
2MGOMAG COATING THROUGHOUT
20SSS
998.1SAV
184.3TF
513.3SAV
0AMHA 0665
0MWL
0MWM
998SSS
994TF
649.8TF
1000.4AMHA 0664

Properties (7)

additional_info
630098021022051
custom_field_three
SPALLING, AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-02-10T11:00:01-08:00
documentation
PROPIPE
is_lateral_inspection
false