Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 25, 2022, 05:30 PM
  • A 0582_A 0581_02252022_100326.mp4

Date
02/25/2022
W/O
936573
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00316
PipeID
P07787
Time
9:30 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9910
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
33
Purpose
Routine Assessment
Project
WO_936573_TV21027_FEB2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
72 in.
Width
15 in.
Upstream MH
A 0582
Downstream MH
A 0581
Dir. of Survey
Downstream
Length Surveyed
895.9 ft.
Total Length
895.9 ft.
Structural Index
3
Structural Quick
3c2c
Structural Rating
890
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
890
Pipe schematic from manhole A 0582 to A 0581
MH: A 0582MH: A 0581downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05822.2 ft. MGO - General Observation - MAG COAT2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start892.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish892.9 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish895.9 ft. AMH - Downstream Manhole, Survey Ends - A 0581

Observations (9)

DistanceCodeObservation
0MWM
892.9SAV
0MWL
2.2MGOMAG COAT
2.2SAV
892.9SSS
2.2SSS
895.9AMHA 0581
0AMHA 0582

Properties (7)

additional_info
630138022522051
custom_field_three
AGGREGATE VISIBLE, SPALLING
custom_field_two
3
customer
1
datetime
2022-02-25T09:30:00-08:00
documentation
PROPIPE
is_lateral_inspection
false