Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 4, 2022, 11:25 AM
  • 01 0017_01 0016_04042022_044128.mp4

Date
04/04/2022
W/O
946704
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00682
Time
4:25 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10052
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_946704_TV01245_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
01 0017
Downstream MH
01 0016
Dir. of Survey
Downstream
Length Surveyed
428 ft.
Total Length
428 ft.
Structural Index
3
Structural Quick
4P3P
Structural Rating
757
O&M Index
2
O&M Quick
2P00
O&M Rating
170
Overall Index
3
Overall Quick
Overall Rating
927
Pipe schematic from manhole 01 0017 to 01 0016
MH: 01 0017MH: 01 0016downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 01 00172 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start261.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN333.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN387.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"423.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish426 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish426 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish426 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish427 ft. MGO - General Observation - ROACHES @ MH428 ft. AMH - Downstream Manhole, Survey Ends - 01 0016

Observation photos (3)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    261.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    333.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

Observations (18)

DistanceCodeObservation
2DAGS
426CM
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
426SSS
2CM
427MGOROACHES @ MH
2SSS
426DAGS
428AMH01 0016
0MWM
261.6TBOPEN
0MWL
387.4TB
333.3TBOPEN
8FM
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
0AMH01 0017
423.3FM

Properties (7)

additional_info
630074040422203
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-04-04T04:25:14-07:00
documentation
PROPIPE
is_lateral_inspection
false