Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2022, 08:49 AM
  • 01 0555_01 0554_03222022_015555.mp4

Date
03/22/2022
W/O
941472
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01044
Time
1:49 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10015
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
FLORENCE-GRAHAM
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_941472_TV01232_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
12 in.
Upstream MH
01 0554
Downstream MH
01 0555
Dir. of Survey
Upstream
Length Surveyed
54.1 ft.
Total Length
54.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 01 0554 to 01 0555
MH: 01 0554MH: 01 0555upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 05550 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MH2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish32.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"49.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start52.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start52.1 ft. MMC - Material Change, Vitrified clay pipe54.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK54.1 ft. MWM - Water Mark, 50 %of cross sectional area54.1 ft. MGO - General Observation - COCKROACHES IN MH54.1 ft. AMH - Downstream Manhole, Survey Begins - 01 055454.1 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Material Change, Vitrified clay pipe

    2 ft. - Material Change, Vitrified clay pipe

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    54.1 ft. - General Observation - COCKROACHES IN MH

Observations (14)

DistanceCodeObservation
2DAGS
54.1AMH01 0555
0MGOCONNECTION AT MH 3 O'CLOCK
0MWM
0MGOCOCKROACHES IN MH
21.3TFC
0AMH01 0554
2MMC
54.1MGOCONNECTION AT MH 3 O'CLOCK
52.1CM
0MWL
52.1DAGS
54.1MGOCOCKROACHES IN MH
4.3CM

Properties (7)

additional_info
630138032122201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-03-22T01:49:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false