Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2022, 08:36 AM
  • 01 0554_01 0553_03222022_014903.mp4

Date
03/22/2022
W/O
941472
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01043
Time
1:36 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10015
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
FLORENCE-GRAHAM
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_941472_TV01232_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
12 in.
Upstream MH
01 0553
Downstream MH
01 0554
Dir. of Survey
Upstream
Length Surveyed
296.7 ft.
Total Length
296.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0553 to 01 0554
MH: 01 0553MH: 01 0554upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 05540 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish2.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish63.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"80.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"149.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"194.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"221.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"257.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"260.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start294.7 ft. MMC - Material Change, Vitrified clay pipe294.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start296.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK296.7 ft. MWM - Water Mark, 40 %of cross sectional area296.7 ft. MWL - Water Level, 25 %of cross sectional area296.7 ft. MGO - General Observation - COCKROACHES IN MH296.7 ft. AMH - Downstream Manhole, Survey Begins - 01 0553

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Material Change, Vitrified clay pipe

    2 ft. - Material Change, Vitrified clay pipe

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    296.7 ft. - General Observation - COCKROACHES IN MH

Observations (21)

DistanceCodeObservation
294.4DAGS
233.5TFC
296.7AMH01 0554
0MGOCONNECTION AT MH 3 O'CLOCK
102.3TFC
294.4CM
0MWM
171.1TFC
39.2TFC
296.7MGOCOCKROACHES IN MH
2MMC
75.2TFC
216TFC
2DAGS
4.5CM
36.5TFC
0MWL
147.6TFA
0MGOCOCKROACHES IN MH
0AMH01 0553
296.7MGOCONNECTION AT MH 3 O'CLOCK

Properties (7)

additional_info
630138032122201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-03-22T01:36:05-07:00
documentation
PRO PIPE
is_lateral_inspection