Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2022, 04:56 AM
  • 01 0524_01 0523_03172022_221125.mp4

Date
03/17/2022
W/O
941472
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01009
Time
9:56 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10012
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_941472_TV01232_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0524
Downstream MH
01 0523
Dir. of Survey
Downstream
Length Surveyed
320.9 ft.
Total Length
320.9 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 01 0524 to 01 0523
MH: 01 0524MH: 01 0523downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 05242 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start27.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"30.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"75.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"77.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"126 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"176.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"179.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"227.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"230.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"275 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"277.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"280.7 ft. H - Hole, from 10 to 12 o'clock, within 8 inches of joint: YES282.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6"318.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish318.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish320.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK320.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0523320.9 ft. MGO - General Observation - COCKROACHES IN MH

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole, from 10 to 12 o'clock, within 8 inches of joint: YES

    280.7 ft. - Hole, from 10 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MH

    320.9 ft. - General Observation - COCKROACHES IN MH

Observations (25)

DistanceCodeObservation
126TFC
0MWL
77.8TF
318.5DAGS
30.4TFC
176.4TFC
227.1TFC
0MWM
75.4TFC
179.2TFC
2.2CM
2DAGS
230.1TFC
320.9MGOCONNECTION AT MH 9 O'CLOCK
128.8TFC
27.5TFC
320.9AMH01 0523
275TBA
277.8TFC
320.9MGOCOCKROACHES IN MH
0MGOCOCKROACHES IN MH
318.5CM
280.7H
282.6TB
0AMH01 0524

Properties (7)

additional_info
630138031722201
custom_field_three
HOLE/CRACKS
custom_field_two
2
customer
1
datetime
2022-03-17T21:56:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false