Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2022, 04:17 AM
  • 01 0518_01 0517_03172022_213234.mp4

Date
03/17/2022
W/O
941472
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01002
Time
9:17 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10012
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_941472_TV01232_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0518
Downstream MH
01 0517
Dir. of Survey
Downstream
Length Surveyed
318.6 ft.
Total Length
318.6 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
1
O&M Quick
2112
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 0518 to 01 0517
MH: 01 0518MH: 01 0517downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05182 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start68.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"77.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"99.6 ft. RFJ - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES99.6 ft. B - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES101.6 ft. RFL - Roots Fine Lateral, from 08 to 11 o'clock101.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"134.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"152.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"179.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"197.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"203.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"230.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"250.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"253.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"280.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"305.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"313.9 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"316.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish318.6 ft. MGO - General Observation - COCKROACHES IN MH318.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0517

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES

    99.6 ft. - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

    99.6 ft. - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Lateral, from 08 to 11 o'clock

    101.6 ft. - Roots Fine Lateral, from 08 to 11 o'clock

  • General Observation - COCKROACHES IN MH

    318.6 ft. - General Observation - COCKROACHES IN MH

Observations (27)

DistanceCodeObservation
305.1TFC
99.6RFJ
99.6B
0MGOCONNECTION AT MH 3 O'CLOCK
250.9TFC
313.9TFA
8.8CM
0MWM
318.6MGOCOCKROACHES IN MH
0MWL
0AMH01 0518
253.8TFC
230.4TFC
2DAGS
316.8CM
101.6RFL
152.5TFC
68.2TFA
134.5TFC
197.4TFA
316.8DAGS
280.6TFC
203.3TFC
101.6TFA
77.4TFC
318.6AMH01 0517
179.4TFC

Properties (7)

additional_info
630138031722201
custom_field_three
BROKEN PIPE/CRACKS
custom_field_two
2
customer
1
datetime
2022-03-17T21:17:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false