Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2022, 05:45 AM
  • 15 1055_15 1054_03282022_225842.mp4

Date
03/28/2022
W/O
947049
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00631
PipeID
P12815
Time
10:45 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10022
Sewer Name
15 SLACK ROAD TRUNK
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_947049_TV15031_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 1054
Downstream MH
15 1055
Dir. of Survey
Upstream
Length Surveyed
326.8 ft.
Total Length
326.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 15 1054 to 15 1055
MH: 15 1054MH: 15 1055upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 10551.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish42.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"47.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"141.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"169 ft. TBC - Tap Break-In Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"174.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"215 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"225 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"290.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"324.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start326.8 ft. MWL - Water Level, 40 %of cross sectional area326.8 ft. AMH - Downstream Manhole, Survey Begins - 15 1054326.8 ft. MWM - Water Mark, 50 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
326.8AMH15 1055
157.8TBC
35.9TFA
279.2TFC
0MWL
284.3TFA
325.5DAGS
185.2TBA
111.8TFA
0AMH15 1054
101.8TFC
0MWM
152.5TFC
203.2TFC
198.2TFA
2DAGS

Properties (7)

additional_info
630138032822201
custom_field_three
RFIR
custom_field_two
3
customer
1
datetime
2022-03-28T22:45:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false