Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2022, 05:11 AM
  • 15 1052_15 1051_03282022_222645.mp4

Date
03/28/2022
W/O
947049
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00631
PipeID
P12811
Time
10:11 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10022
Sewer Name
15 SLACK ROAD TRUNK
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_947049_TV15031_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 1052
Downstream MH
15 1051
Dir. of Survey
Downstream
Length Surveyed
240.3 ft.
Total Length
240.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 15 1052 to 15 1051
MH: 15 1052MH: 15 1051downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 10520 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start14.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"63.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"102.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"113 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"215.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"238 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish240.3 ft. MGO - General Observation - COCKROACHES IN MH240.3 ft. MGO - General Observation - TROUGH DAMAGE240.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK240.3 ft. AMH - Downstream Manhole, Survey Ends - 15 1051

Observation photos (4)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    240.3 ft. - General Observation - COCKROACHES IN MH

  • General Observation - TROUGH DAMAGE

    240.3 ft. - General Observation - TROUGH DAMAGE

Observations (17)

DistanceCodeObservation
113TFC
0MGOCONNECTION AT MH 3 O'CLOCK
63.6TFA
215.5TFA
240.3MGOCOCKROACHES IN MH
14.7TFC
2DAGS
238DAGS
240.3MGOTROUGH DAMAGE
166.4TFA
0AMH15 1052
0MGOCOCKROACHES IN MH
240.3MGOCONNECTION AT MH 3 O'CLOCK
0MWL
102.5TBA
240.3AMH15 1051
0MWM

Properties (7)

additional_info
630138032822201
custom_field_three
RFIR
custom_field_two
3
customer
1
datetime
2022-03-28T22:11:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false