Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2022, 06:30 AM
  • 15 1049_15 1048_03282022_234031.mp4

Date
03/28/2022
W/O
947049
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00631
PipeID
P12808
Time
11:30 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10022
Sewer Name
15 SLACK ROAD TRUNK
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_947049_TV15031_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 1049
Downstream MH
15 1048
Dir. of Survey
Downstream
Length Surveyed
255.8 ft.
Total Length
255.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 15 1049 to 15 1048
MH: 15 1049MH: 15 1048downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 10490 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start35.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"84.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"186.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.6 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"235.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"253.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish255.8 ft. MGO - General Observation - COCKROACHES IN MH255.8 ft. AMH - Downstream Manhole, Survey Ends - 15 1048255.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    255.8 ft. - General Observation - COCKROACHES IN MH

Observations (16)

DistanceCodeObservation
0MWL
0MWM
0AMH15 1049
255.8MGOCOCKROACHES IN MH
35.4TFA
253.9DAGS
195.6TBA
235.5TFA
0MGOCOCKROACHES IN MH
137.5TFA
255.8AMH15 1048
2DAGS
255.8MGOCONNECTION AT MH 3 O'CLOCK
0MGOCONNECTION AT MH 3 O'CLOCK
84.7TFA
186.7TFC

Properties (7)

additional_info
630138032822201
custom_field_three
RFIR
custom_field_two
3
customer
1
datetime
2022-03-28T23:30:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false