Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2022, 08:40 AM
  • 01 1222_01 1221_04052022_015425.mp4

Date
04/05/2022
W/O
947045
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00226
PipeID
P02136
Time
1:40 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10053
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
CUDAHY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_947045_TV01206_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 1221
Downstream MH
01 1222
Dir. of Survey
Upstream
Length Surveyed
271.3 ft.
Total Length
271.3 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
159
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
162
Pipe schematic from manhole 01 1221 to 01 1222
MH: 01 1221MH: 01 1222upstream0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 01 122244.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"157.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.8 ft. RMC - Roots Medium Connection, from 02 to 04 o'clock, 15 %, within 8 inches of joint: YES159.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"262.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start271.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK271.3 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK271.3 ft. AMH - Downstream Manhole, Survey Begins - 01 1221271.3 ft. MWM - Water Mark, 25 %of cross sectional area271.3 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 02 to 04 o'clock, 15 %, within 8 inches of joint: YES

    111.5 ft. - Roots Medium Connection, from 02 to 04 o'clock, 15 %, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    111.5 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    171.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    226.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (13)

DistanceCodeObservation
226.9TB
0MGOCONNECTION AT THE MH 3 OC'LOCK
111.5RMC
0MGOCONNECTION AT THE MH 9 OC'LOCK
271.3CM
0AMH01 1221
8.5CM
0MWM
171.6TB
111.5TB
271.3AMH01 1222
0MWL
113.9TF

Properties (7)

additional_info
630074040422201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-04-05T01:40:35-07:00
documentation
PROPIPE
is_lateral_inspection
false