Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2022, 08:25 AM
  • 01 1221_01 1220_04052022_013906.mp4

Date
04/05/2022
W/O
947045
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00226
PipeID
P02135
Time
1:25 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10053
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
CUDAHY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_947045_TV01206_APR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 1221
Downstream MH
01 1220
Dir. of Survey
Downstream
Length Surveyed
253.5 ft.
Total Length
253.5 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
60
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
60
Pipe schematic from manhole 01 1221 to 01 1220
MH: 01 1221MH: 01 1220downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 12210 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area83 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES125.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.8 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES129.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start180 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"221.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish253.5 ft. AMH - Downstream Manhole, Survey Ends - 01 1220

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    83 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    126.8 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    129.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    180 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (13)

DistanceCodeObservation
126.8CM
129.1TF
221.9CM
0AMH01 1221
83CM
253.5AMH01 1220
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MGOCONNECTION AT THE MH 9 OC'LOCK
129.8CM
180TB
125.6TF
0MWM
0MWL

Properties (7)

additional_info
630074040422201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-04-05T01:25:22-07:00
documentation
PROPIPE
is_lateral_inspection
false